Simplex 4606-9101 LCD Annunciator
The Simplex 4606-9101 is a remote LCD Annunciator designed to mirror fire alarm control panel information at a location away from the main panel. It allows building staff and emergency personnel to monitor and control system status from a convenient entry point, like a lobby or guard station.
Category Addressable Fire Alarm System
Brand: Simplex
Description
Electrical Specifications
- Operating Voltage: 18 to 32 VDC (supplied by the main fire alarm control panel).
- Normal Operating Current: 110 mA with the LCD backlighting turned on.
- Battery Standby Current: 65 mA. The LCD backlighting automatically powers down after 30 seconds of switch inactivity to preserve battery power.
- Alarm Current: 140 mA maximum (occurs when the backlighting is active and the local tone-alert piezo is sounding).
Communication & Wiring Requirements
- Protocol/Data Line: Communicates over the N2 format external annunciator communication line.
- Data Wiring: Requires a single twisted, shielded pair (STP) or unshielded twisted pair (UTP) depending on local environment noise. Conductor sizes range from 18 AWG to 12 AWG.
- Power Wiring: Requires two 18 AWG to 12 AWG wires plus a dedicated Earth Ground connection routed directly to each metal electrical box for transient suppression.
- Maximum Distance: Up to 4,000 feet (1,219 meters) from the control panel using 18 AWG conductors.
- Line Termination: Requires a 100 Ω, 1/2 W line matching resistor harness (Model 4081-9011) at the end-of-line device.
Environmental Limitations
- Operating Temperature: 32°F to 120°F (0°C to 49°C).
- Operating Humidity: Up to 93% Relative Humidity (RH), non-condensing at 100°F (38°C).
Be the first to review “Simplex 4606-9101 LCD Annunciator” Cancel reply
Related
Related Products
Related products
-

-

-

-

-

-
Sale!

GST-DI-9103E Intelligent Rate of Rise and Fixed Temperature Heat Detector
QAR90.00Original price was: QAR90.00.QAR85.00Current price is: QAR85.00.

Reviews